Electrical Panel Requirements
NEC Code for electrical panel requirements is not a complete electrical reference for services, installations or repairs. Some cities have more strict code standards. Electrical Panel Requirements do change from time to time. Always use electricians that are certified by the State of California. Electrical Panel Requirements and Your Safety is Our Top Priority.
      
Meter Height
The height of the meter shall be between 48 inch and 66 inch above the ground.
 
Bonding
Bonding of the hot, cold, and gas lines is required when the electrical panel is replaced. Bonding shall consist of a continuous bond jumper installed at the water heater between the hot, cold, and gas lines.
 
Working Space
The clear working space in front of the panel shall be 30 inch wide by 36 inch deep with a minimum headroom clearance of 6 feet - 6 inch (Article 110.26)
 
Grounding of Services
Electrical Grounding System shall consist of a continuous grounding electrode conductor run from the panel to a ground rod (grounding electrode) and to the cold water pipe. Grounding of the electrical service at the main water line must be within the first 5 feet of water piping into the building. The underground water service shall not be used as the grounding electrode without supplemental electrode. [Article 250.53 (d)]

For existing structures and additions not affecting the main electrical service panel location, the grounding electrode shall be nonferrous (copper), listed, and not be less than 1/2 inch in diameter. The electrode shall be installed such that at least 8 feet of length is in contract with the soil. The upper end of the electrode shall be flush with or below ground level unless the above-ground end and the grounding electrode conductor attachment is protected against physical damage.
 
SERVICE ENTRANCE CONDUCTORS SIZE AND RATING
Service or
Feeder Rating
Copper
Conductors
Aluminum or
Copper-Clad
Aluminum
Minimum
Conduit
Size
100 Amps
#4 AWG
#2 AWG
1 1/4 inch
125 Amps
#2 AWG
#1/0 AWG
1 1/4 inch
150 Amps
#1 AWG
#2/0 AWG
1 1/4 inch
200 Amps
#2/0 AWG
#4/0 AWG
1 1/2 inch
GROUNDING ELECTRODE CONDUCTOR SIZING (Table 250.66)
Size of Main
Panel
Copper
Conductors
Aluminum or
Copper-Clad
Aluminum
100 Amps
#8 AWG
#6 AWG
125 Amps
#8 AWG
#6 AWG
150 Amps
#6 AWG
#4 AWG
200 Amps
#4 AWG
#2 AWG
GROUNDING ELECTRODE CONDUCTOR SIZING (Table 250.66)
Size of Main
Panel
Copper
Conductors
Aluminum or
Copper-Clad
Aluminum
100 Amps
#8 AWG
#6 AWG
125 Amps
#6 AWG
#4 AWG
150 Amps
#6 AWG
#4 AWG
200 Amps
#6 AWG
#4 AWG

 